機櫃式水冷板散熱模組 In-Rack CDU / 設備規格 Mechanical Specifications |
冷卻單元尺寸 CDU Dimensions |
Height: 4U, Width: 48cm, Depth: 75cm |
冷卻單元重量 CDU Weight |
Dry: 55kg / Wet: 60kg |
運轉環境需求 Ambient Requirements |
Storage and Transport: -40 - 70℃(-40 - 158℉), RH < 90% |
電器規格 Electrical Specifications |
電源 Power Input |
AC100V - AC240V, 50/60Hz |
輸出/通訊/人機介面 |
1.Modbus 2.VNC Server 3. Email Alarm |
Output/Communication/Human Interface |
散熱規格 Thermal Specifications |
冷卻能力 Cooling Capacity |
80 kW at 32℃(89.6℉) facilities supply at 12.7 m3/hr (56GPM) |
冷卻液 Coolant |
Glycol Water |
冷卻液最高溫度 Server Cooling Fluid |
Max. Temperature 60℃(140℉) |
設施要求條件 Facilities Water Requirements |
水溫 Water Temperature |
Dew Point T. < 45℃ |
水壓 Facilities Water Pressure |
Max. 10 Bar |
容許顆粒尺寸 Particulates |
Max. Particulates Diameter < 0.2 mm |